Terasun Europe
Fire protection — Terasun TSM

Terasun TSM — Fire protection

🔥 Fire protection

Fire-resistant cement board partitions

The Terasun TSM fire-rated wall system achieves E 120, EI 90, and EW 120 classifications per FIRES-CR-284-25-AUPE.

E 120EI 90EW 120

Application

Independently tested fire-rated partition systems achieving E120, EI90, and EW120 fire resistance classifications.

BoardTerasun TSM 12 mm — both faces
Fire classA1
Fire assembly ratingE 120 / EI 90 / EW 120
Test reportFIRES-CR-284-25-AUPE
FrameSteel C-studs 75–100 mm
Stud spacing400 mm c/c
InsulationMineral wool · min. 60 kg/m³ · continuous fill
ETAETA 24/0895

Source: ETA 24/0895 · DoP TRS-20250610F · CE 1023-CPR-1565 P · FIRES-CR-284-25-AUPE · EN 12467

Fire performance features

✓

E 120 — integrity 120 minutes

✓

EI 90 — integrity and insulation 90 minutes

✓

EW 120 — integrity and radiation limitation 120 minutes

✓

Independently tested — FIRES-CR-284-25-AUPE

✓

CE certified for fire performance under the EU Construction Products Regulation

✓

Suitable for commercial, public, and industrial occupancies

Suitable for commercial, public, and industrial buildings. Specifications should reference the tested system configuration.

Downloads for this System

6 documents · 0 available immediately

Open Download Centre →
PDF

Fire Test Report

Loading…
PDF

Tested Wall Assemblies Guide

Loading…
PDF

Fire-Rated Wall Installation Manual

Loading…
PDF

European Technical Assessment

Loading…
PDF

CE Certificate

Loading…
PDF

Declaration of Performance — TRS-20250610F

Loading…